产品名称:ZW20-12 10KV High voltage vacuum circuit breaker on outdoor column
产品应用: Product overviewZW20 outdoor high-voltage AC vacuum circuit breaker is an outdoor high-voltage switchgear with rated
E-mail:sales@feidadq.com
热线电话: 400-610-8160
Product overview
Number |
|
|
Number | |
l | nominal voltage | kV | 12 | |
2 | rated current | A | 630 | |
3 | rated frequency | Hz | 50 | |
4 |
|
kA | 50 | |
5 | Rated short-time withstand current | kA | 20 | |
6 | Rated short circuit switching current | kA | 20 | |
7 | Rated short-circuit closing current (peak) | kA | 50 | |
8 |
|
S | 4 | |
9 | rated | lmin Power frequency withstand voltage (effective value)(wet) dry phase, ground/fracture | kV | (34)42/48 |
insulation | Rated lightning) medium impact pressure (peak) phase, to the ground/fracture | kV | 75/85 | |
level | Secondary loop LMIN power frequency withstand voltage | kV | 2 | |
10 |
|
O-0.3s-CO-180s-CO | ||
ll | Rated short circuit current switching times | second-rate | 30 | |
12 | mechanical life | second-rate | 10000 |
Number |
|
|
|
l | clearance between open contacts | mm | 9±l |
2 |
|
mm | 3±l |
3 | opening time | mS | 18~45 |
4 | closing time | mS | 20~60 |
5 |
|
mS | ≤2 |
6 | The switching and closing of the three-phase system is out of synchronization | mS | ≤2 |
7 | Average breaking speed | m/S | 1.2±0.2 |
8 | Average closing speed | m/S | 0.6±0.2 |
9 | Main circuit resistance (excluding cable) | LlQ | ≤120 |