产品名称:S11-M/10 S11 Series 10KV oil-immersed distribution transformers
产品应用: Product introduction:The product is subject to the national standard GB1094-1996 Power Transformer and GB T6451-2008
E-mail:sales@feidadq.com
热线电话: 400-610-8160
Temperature: temperature: * * + 40 ℃, * * : the average daily temperature + 30 ℃, annual average temperature: * * + 20 ℃, the temperature: * * - 25 ℃.
The elevation of the transformer installation site shall not exceed 1000m, and the temperature rise limit shall be corrected if it exceeds 1000m.
The installation site shall be free from gas, steam, chemical deposit dust, dirt and other explosive and erosive substances that seriously affect the insulation of the transformer
No serious vibration or turbulence in the installation site
Technical parameters:
|
|
Voltage combination (KV) | No-load loss (W) |
Load loss (W) |
No-load Current (%) |
A short circuit Impedance (%) |
||
High pressure |
|
Low tension | ||||||
S11-M-30 | Yyn0 and Dyn11 |
6 6.3 10 10.5 11 |
±5% and ±2×2.5% |
0.4 | 100 | 600 | 2.10 | 4 |
S11-M-50 | 130 | 870 | 2.00 | |||||
S11-M-80 | 180 | 1250 | 1.80 | |||||
S11-M-100 | 200 | 1500 | 1.60 | |||||
S11-M-125 | 240 | 1800 | 1.50 | |||||
S11-M-160 | 280 | 2200 | 1.40 | |||||
S11-M-200 | 340 | 2600 | 1.30 | |||||
S11-M-250 | 400 | 3050 | 1.20 | |||||
S11-M-315 | 480 | 3650 | 1.10 | |||||
S11-M-400 | 570 | 4300 | 1.00 | |||||
S11-M-500 | 680 | 5150 | 1.00 | |||||
S11-M-630 | 810 | 6200 | 0.90 | 4.5 | ||||
S11-M-800 | 980 | 7500 | 0.80 | |||||
S11-M-1000 | 1150 | 10300 | 0.70 | |||||
S11-M-1250 | 1360 | 12000 | 0.60 | 4.5 | ||||
S11-M-1600 | 1640 | 14500 | 0.60 |