产品名称:ZGS11 10KV American trunk transformer
产品应用: Product center This series of combined substations are 35kV on the high voltage side, 10kV, 6kV and 0 4kV on
E-mail:sales@feidadq.com
热线电话: 400-610-8160
Product center
This series of combined substations are 35kV on the high voltage side, 10kV, 6kV and 0.4kV on the low voltage side, three-phase AC 50Hz outdoor complete equipment, generally suitable for some large construction sites, as the reception, conversion and distribution of electrical energy, is an economical, affordable, easy to flow transportation and fixed installation of new substations.
Service environment:
1、Ambient temperature: -25℃~+40℃;
2、Altitude: ≤1000m, 3000m if special ordered transformer and low-voltage components are used;
3、Vertical tilt: ≤3°;
4、Relative humidity: ≤90% (+25℃);
5、Household pressure: ≤700 Pa;
6、No conductive dust, corrosive gas, explosion, fire and violent shaking place.
Technical parameters:
|
Switch cabinet | Breaker | Project |
|
|
|
High voltage unit | 40.5kV | KYN10-40.5 XGN17-40.5 KYN61-40.5 |
ZN85-40.5 ZN12-40.5 LN2-35(Z) VEP-40.5 FP-40.5等 |
Nominal voltage | kV | 40.5 |
Rated current | A | 1250-2500 | ||||
Rated short circuit switching current | kA | 20-31.5 | ||||
Rated short-circuit closing current (peak) | kA | 50-80 | ||||
Load switch NAL36 |
Rated current | A | 630 | |||
Rated short-time withstand current | kA/S | 25/2 | ||||
Low pressure unit | 12KV |
KYN28-12 XGN2-12 KZN1-12 KYN1-12 PIX |
ZN28-12、VD4、VS1、VBG、HVX等 | Nominal voltage | kV | 12 |
Rated current | A | 630-3150 | ||||
Rated short-circuit switching current (EFFECTIVE value) | kA | 16-50 | ||||
Rated short-circuit closing current (peak) | kA | 40-125 | ||||
HXGN11-12(F) HXGN26-12(F) |
Load at the beginning FN16-12 FN26-12 FN26-12 R |
Rated current | A | 630 | ||
Rated short-time withstand current | kA/S | |||||
0.4kV | GGD GCK GCS MNS |
DW15、DW17、ME、M、DZ20、CM、H、S系列 | Circuit breaker rated current | A | ≤4000A | |
On-off capacity (400V) | kA | 28-80 | ||||
|
SC9, S9, SZ9, SZ11, S11 and other series transformers | Nominal voltage | kV | 40.5 | ||
Rated capacity | kVA | 400-20000 | ||||
No-load voltage ratio | kV/kV | 35/10、35/6.3,35/0.4 | ||||
Box | Enclosure protection class | IP54 | ||||
Sound level | dB | ≤55 |